UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
3 Installation
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
45
Item
360 kVA
400 kVA
440 kVA
480 kVA
Recommended
cross-sectional
area (mm
2
)
U
2 x (4 x 185)
2 x (4 x 240)
3 x (4 x 185)
3 x (4 x 240)
V
W
N
PE
185
240
240
240
Battery
input
Nominal discharge
current (384 V current;
thirty-two 12 V
batteries) (A)
987
1096
1206
1316
Maximum discharge
current (end of
discharge current of
thirty-two 12 V
batteries, namely, 1.67
V/cell discharge current
of 192 2 V cells) (A)
1181
1321
1443
1574
Recommended
cross-sectional
area (mm
2
)
+
3 x 150
3 x 185
3 x 185
3 x 240
N
3 x 150
3 x 185
3 x 185
3 x 240
-
3 x 150
3 x 185
3 x 185
3 x 240
PE
150
185
185
240
When there is one mains input, configure input cables as mains input cables.
Additionally, cables listed in
are available only under the following conditions:
Routing mode: Routed over the ladder or bracket in a single layer (the routing mode for DC cables is
F in IEC60364-5-52 and the routing mode for AC cables is E in IEC60364-5-52).
Ambient temperature: 30°C.
The drop amplitude of AC voltage is less than 3% and DC voltage less than 1%. It is recommended
that AC power cables be no longer than 30 m and DC power cables be no longer than 50 m.
70°C copper flexible cable.
If external conditions such as cable layout or ambient temperatures change, perform verification in
accordance with the IEC-60364-5-52 or local regulations.
When selecting, connecting, and routing power cables, follow local safety regulations and rules.
The currents listed in
are measured at a rated voltage of 380 V; if the rated voltage is 400 V,
multiply the currents by 0.95; if the rated voltage is 415 V, multiply the currents by 0.92.
If primary loads are non-linear loads, increase the cross-sectional areas of neutral wires 1.5–1.7 times.