UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
3 Installation
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
64
Installing a UPS in Channel Steels
Ensure that the installation channel steels is flat.
Step 1
According to required mounting hole dimensions at the cabinet base, the channel steal spacing
is 800 mm, and the hole spacing is 732 mm. The recommended channel steal width is 50 mm
or more. Determine the position for installing the cabinet on the channel steal, as shown in
Figure 3-24
Installing a base on the channel steel (Unit of measurement :mm)
(1) Channel steel mounting hole
(2) Channel steel
(3) Column
(4) Base
The external sides of front and rear channel steels must be aligned with the column. The
channel steel spacing is 800 mm. The recommeneded channel steel width is 50 mm or
more.
Cabinet mounting holes must align channel steels. Tighten screws to secure the base to
channel steels.
Step 2
Drill holes in the mounting hole marks by using a hammer drill.