UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
4 User Interface
Issue 06 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
143
Figure 4-55
Basic Parameters 2
−
Number of CIMs
A maximum of four CIMs can be connected.
−
CIM start address
The CIM start address cannot be changed. The DIP switch should be set to 0000 for
the first CIM, and the DIP switch setting for a later connected CIM should increase
by 1 (binary) than that set for the previous CIM.
−
CIM Number of BIMs
Number of BIMs managed by the CIM. One CIM can support a maximum of 300
BIMs.
−
Number of battery strings
The No. of battery string connected to the UPS. A maximum of four battery strings
can be connected.
−
Batteries in a single battery string
Number of batteries in a battery string. A battery string contains a maximum of 300
batteries.
−
CIM logical start addr
Communication start address when the northbound device queries CIM data.
Advanced Param.
screen.