UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
3 Installation
Issue 06 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
43
3.1.1.2 Installation Environment
Do not install the UPS in high temperature, low temperature, or damp environments.
Install the UPS away from water sources, heat sources, and flammable or explosive
materials. Keep the UPS away from direct sunlight, dust, volatile gases, corrosive
materials, and air dense with salt particles.
Do not install the UPS in environments with conductive metal scraps in the air.
The optimal operating temperatures for valve-regulated lead-acid batteries (VRLA
batteries) are 20–30°C. Operating temperatures higher than 30°C shorten the battery
lifespan and operating temperatures lower than 20°C reduce the battery backup time.
3.1.1.3 Installation Clearances
Reserve the following clearances around the cabinet to facilitate operations and ventilation:
Reserve at least 800 mm from the front of the cabinet to facilitate ventilation and
operations. Reserve at least 500 mm from the rear of the cabinet for facilitate ventilation.
Reserve at least 500 mm from the top of the cabinet for operations.
shows the installation clearances.
Figure 3-2
Reserved clearances (unit: mm)
3.1.2 Tools and Instruments