UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
3 Installation
Issue 06 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
68
3.2.6 Routing Cables (UPS5000-E-125K-FM)
3.2.6.1 Routing Cables from the Top
Context
Before connecting cables, ensure that the switches inside the UPS, the upstream input
switch and battery string switch are OFF to prevent operations with power on.
Route cables for the UPS from inside out and from bottom up.
The wiring diagram in this section uses cable routing by removing small covers as an
example. For the cable routes of cable routing by drilling holes, refer to this section.
Procedure
Step 1
Remove the filler panels from the front of the cabinet.
Figure 3-28
Removing filler panels
Step 2
Determine the cabling mode.
Remove the cable tray covers from the top of the cabinet for cable routing.
Remove the small covers from the top of the cabinet, as shown in