UPS5000-S-1200 kVA
User Manual
4 User Interface
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
117
Figure 4-30
Battery settings 3
Item
Description
Default Value Value Range
Battery string
sharing
Two power units share battery
strings.
Disable
Disable, Enable
Battery type
Currently, only lead-acid
batteries are supported.
-
-
Single battery
voltage (V)
Specifies the voltage of each
battery that is connected in the
battery string in series.
12V
2, 6, 12
Single battery
capacity (Ah)
Specifies the capacity of each
battery that is connected in the
battery string in series.
Depends on the
actual model.
5–9999
Batteries in a
battery string
Specifies the number of batteries
in a battery string.
2 V battery:
240
6 V battery:
80
12 V battery:
40
2 V battery:
180–300
6 V battery:
60–100
12 V battery:
30–50
Number of
battery strings
Specifies the number of battery
strings connected in parallel.
1
1–4
Installation
time
A battery maintenance reminder
is displayed when the
maintenance time (counted from
the installation time) comes.
-
-
Maintenance
period (d)
Specifies the interval for
reminding users of battery
maintenance.
If this parameter is set to
0
, there
is no reminder.
0
0–365
Chg. cur.
limiting coef.
The charging current limit is a
multiple of the battery capacity.
0.1C10
0.05C10 to
0.15C10