UPS5000-S-1200 kVA
User Manual
4 User Interface
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
120
Item
Description
Default Value Value Range
current.
sensor 600A,
Hall sensor
1500A
BCB connects
to iBOX
Whether the BCB is connected to
the iBOX.
Disable
Disable, Enable
Batt. abnormal
BCB trip
Whether the BCB trips when
batteries are abnormal.
Disable
Disable, Enable
Multi-Hall cur.
setting
Multi-Hall cur. setting
is equal
to the number of Hall effect
sensors at the positive or negative
terminal of a battery string
(Multi-Hall cur. setting ≥ 1).
1
1–8
Figure 4-34
Battery string configuration
Set the iBOX and iBAT number for each battery string.
Dry Contact Settings
Set only the dry contacts that are needed. Otherwise, the UPS may not run properly.
When a dry contact card is disabled, its dry contact signals are disabled.
After a dry contact card is enabled, its dry contact signals can be displayed on the LCD.
Disable all the dry contacts for a dry contact card that is not connected and all the dry
contacts that are not used to prevent false alarms.
( ) encloses a unit, and [ ] encloses silk screen.
Specify dry contact settings on the following cards: