Signal Name
Description
Unit in the UPS
#CNT_BL
Low battery voltage times
N/A
#INPHASES
Input phases
N/A
#OUTPHASES
Output phases
N/A
When you add a job, five sending methods are available. The latter three methods can take
effect only when the event condition is still true after the specified seconds.
Immediately, once
: After the event happens, the job will be sent to the RCCMD client
immediately.
Scheduled in X seconds
: After the event happens, the job will be sent to the RCCMD
client once in X seconds. No matter whether the event disappears or not within X
seconds, the job will be sent.
After X seconds, repeat all Y Specify the interval
: After the event happens, the job will
be sent once in X seconds, and then be sent once every Y seconds.
After X seconds on Battery
: After the battery mode is activated for X seconds, the job
will be sent to the RCCMD client once.
At X seconds remaining time
: When the battery backup time has only X seconds left,
the job will be sent to the RCCMD client once.
X and Y are variables and stand for time.
RCCMD Certificate Management
After replacing the certificate on the MDU WebUI, replace the certificate on the RCCMD
client too. Otherwise, communication will fail. For details about the replacing method, see
the RCCMD user manual.
The default certificate provided by the system has expired. Replace the certificate
immediately.
After
SSL Encrypted Transmission
is set to
Enable
,
RCCMD Certificate Management
is
displayed. The RCCMD certificate, RCCMD certificate key, and RCCMD CA certificate can
be uploaded, as shown in
. If the RCCMD certificate or RCCMD CA certificate is
not uploaded, the default certificate provided by the system is used for communication. After
the certificate is uploaded successfully, click
Submit
. The WebUI of the MDU will restart,
and the uploaded certificate will be used for communication.