UPS5000-S-1200 kVA
User Manual
5 Operations
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
166
Procedure
Step 1
On the LCD of each power unit, choose
Settings
>
Dry Contacts Set
, set
MUE05A
connection
to
Enable
, and set
BCB connection [OL]
and
Battery breaker [STA]
to
Enable
.
Figure 5-5
BCB connection setting
----End
5.1.6 (Optional) Setting Parameters for the Maintenance Bypass
Unit
Prerequisites
The maintenance bypass cabinet has been configured.
Procedure
Step 1
Choose
System Info > Settings > System Settings
. Set
Maintenance bypass cabinet
to
Enable
.
Figure 5-6
Setting parameters for the maintenance bypass cabinet