UPS5000-S-1200 kVA
User Manual
5 Operations
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
167
----End
5.1.7 (Optional) Setting Parameters for the Fan Unit
Prerequisites
The fan unit has been configured.
Procedure
Step 1
Choose
System Info > Settings > System Settings
. Set
Top outlet fan
to
Enable
.
Figure 5-7
Setting parameters for the top outlet fan
----End
5.2 Shutting Down and Powering Off the UPS
Context
After the inverter is shut down, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is not normal, the UPS supplies no power. Before shutting down the UPS, ensure
that all loads have shut down.
Procedure
Step 1
Shut down the inverter.
Shutting down the inverter on the LCD
On the system LCD, choose
Common Functions
>
Inv. OFF
. After confirmation, the
inverter is shut down.