UPS5000-S-1200 kVA
User Manual
8 Technical Specifications
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
189
8
Technical Specifications
Table 8-1
Technical specifications
Item
Specifications
Cabling mode
Battery cables are routed in and out from the top, and input
and output are connected using busbars.
Protection level
IP20
Communication
Supports dry contacts, RS485 ports, and FE ports. Supports
Simple Network Management Protocol (SNMP).
Dimensions (H x W x D)
2200 mm x 2800 mm x 1000 mm (without a maintenance
bypass unit and fan unit)
2200 mm x 3400 mm x 1000 mm (with a maintenance bypass
unit)
2200 mm x 3600 mm x 1000 mm (with a fan unit)
Weight
2360 kg (without a maintenance bypass unit and fan unit)
2590 kg (with a maintenance bypass unit)
2660 kg (with a fan unit)
Table 8-2
Environmental specifications
Item
Specifications
Operating temperature
0°C to 40°C
Storage temperature
–40°C to +70°C
Relative humidity
0%–95% RH (non-condensing)
Altitude
0–1000 m
The power is derated as described in IEC62040-3 when the
altitude is from 1000 m to 4000 m. The upper limit of the
altitude is 4000 m.