9 (Optional) TN-C System Application
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
194
9
(Optional) TN-C System Application
If the TN-C system is adopted, short-circuit the input N and PE, and connect the input PE and
N to the terminal on the N bar.
Recommended cable cross-sectional area: 240 mm
2
Recommended screw: M16
Figure 9-1
Short-circuiting the input N and PE