UPS5000-S-1200 kVA
User Manual
10 Alarm List
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
199
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name Severity
Cause
Solution
0043-1
Fan abnormal
Critical
The fan for
the power
module is
abnormal.
The fan
monitoring
cable for the
power
module is not
working
properly.
Replace the faulty power module.
0043-2
The fan is faulty.
Check the fan or replace the bypass module.
0043-3
The fan is
faulty.
The fan
monitoring
cable is
faulty.
1.
Replace the fan.
2.
Check the fan monitoring cable.
0043-4
0047-1
Not ready
Critical
The ready switch
is OFF.
Close the ready switch.
0060-4
Inverter
abnormal
Critical
A load
short-circuit
occurs.
A short
circuit occurs
inside the
module. (This
fault seldom
occurs.)
The output is
incorrectly
grounded.
1.
Check load cable distributions.
2.
Check whether the output is grounded.
3.
If the load cable connections are normal
and the output is correctly grounded,
replace the power unit or module.
0061-2
Inverter alarm
Minor
The I2C bus
is not normal.
The
E2PROM is
faulty.
1.
Rectify the fault and check whether the
alarm is cleared.
2.
If the alarm is generated again, replace
the power module.
0061-7
Inverter alarm
Minor
The bypass
waveform is not
normal.
If not all modules generate the alarm,
start the UPS, transfer it to normal
mode, and replace the faulty module.
If all modules generate the alarm, open
the bypass input circuit breaker. After
the inverter relay is closed, close the