UPS5000-S-1200 kVA
User Manual
10 Alarm List
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
202
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name Severity
Cause
Solution
0086-1
Max. number
of BPM
transfers
Minor
The system
frequently
transfers to
bypass mode due
to overload
timeout or load
impact.
Check the load.
0087-1
System
transfer-to-byp
ass
Warning
The neighboring
UPS is not
normal, and
transfers to
bypass mode.
Check the reason why the neighboring UPS
transfers to bypass mode.
0088-1
Rack address
conflict
Critical
The configured
rack address
conflicts with
another one.
Check the rack address setting.
0089-1
Rack output
overload
Minor
The load is
excessive.
The rack
capacity
setting is not
appropriate.
Check the load and remove some loads
or expand the UPS power capacity if the
UPS is overloaded.
Check that the configured rack capacity
meets requirements.
0090-1
Dry contact
board fault
Critical
I2C
communication
with the dry
contact board
MUE05A fails.
Replace the dry contact board MUE05A.
0090-2
I2C
communication
with the dry
contact board
MUE06A fails.
Replace the dry contact board MUE06A.
0356
Battery Mode
Minor
The UPS is
working in
battery mode.
The running status is displayed. See details
about how to handle other alarms.
0359
No power
supplied
Warning
No power is
supplied.
The running status is displayed. See details
about how to handle other alarms.
0332
Output
disabled
Minor
The output is
disabled.
The running status is displayed. See details
about how to handle other alarms.
0337
PDC bypass
input breaker
open
Critical
The bypass input
circuit breaker
on the PDC is
OFF.
The running status is displayed. No further
measures are required.