UPS5000-S-1200 kVA
User Manual
2 Overview
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
20
2.3.3 Power Module
Appearance
Figure 2-11
Power module
(1) Positioning lock
(2) Run indicator
(3) Alarm indicator
(4) Fault indicator
(5) Ready switch
(6) Output port
(7) Input port
Table 2-2
Indicator description
Indicator
Color
Status
Description
Run indicator
Green
Steady on
The system is working in inverter
mode.
Blinking at long
intervals
The inverter is ready and in
standby state (blinking at 0.5
Hz, on for 1s and off for 1s).
The inverter is not started
(blinking at 0.2 Hz, on for 2.5s
and off for 2.5s).
Blinking at short
intervals
The module is not configured, the
inverter or rectifier DSP software
is being upgraded, or the inverter