UPS5000-S-1200 kVA
User Manual
10 Alarm List
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
195
10
Alarm List
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name Severity
Cause
Solution
0001-1
Mains voltage
abnormal
Minor
Cable
connections
are incorrect.
The mains is
not normal.
The power
module is
faulty.
The output or
battery is
incorrectly
grounded.
1.
Check whether cables to mains are
disconnected, loose, or incorrectly
connected.
2.
If cable connections are correct, measure
the mains voltage with a multimeter. If
the mains voltage exceeds 280 V, the
mains input is not normal; if the mains
voltage is less than 272 V, the sampling
circuit of the power module is not
normal. Replace the faulty module.
3.
Check whether the output or battery is
incorrectly grounded.
0001-2
Cable
connections
are incorrect.
The mains is
not normal.
The mains
input fuse for
the power
module is
blown.
1.
Check whether cables to mains are
disconnected, loose, or incorrectly
connected.
2.
If cable connections are correct, measure
the mains voltage with a multimeter. If
the mains voltage is less than 80 V, the
mains voltage is not normal; if the mains
voltage exceeds 88 V, the power module
sampling circuit or fuse may not be
working properly. Replace the faulty
module.
0001-3
The mains is not
normal.
Check the mains.
0004-1
Mains ph.
Reversed
Minor
Cable
connections are
incorrect.
Verify the cable connections.
0005-1
Mains neutral
absent
Minor
Cable
connections are
1.
Secure or connect the neutral wire to the
cabinet if it is loose or disconnected.