UPS5000-S-1600 kVA
User Manual
4 User Interface
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
106
Table 4-9
Bypass input
Item
Description
Phase voltage (V)
Bypass input phase voltage
Line voltage (V)
Bypass input line voltage
Phase current (A)
Bypass input phase current
Frequency (Hz)
Bypass input frequency
Power factor
Proportion of the bypass input active power to the bypass
input apparent power.
Table 4-10
Power Unit N Batt.
Item
Description
Battery status
Battery status, which can be
Not connected
,
Equalized
charging
,
Float charging
,
Hibernating
,
discharging
, or
Not chg. or dis
.
Voltage (V)
Voltage of the battery string
Current (A)
Current of the battery string. The current is
+
when
batteries are being charged and
-
when discharged.
Temperature (°C)
N/A
Backup time (min)
Battery backup time estimated at the current load
Remaining cap. (%)
Remaining battery capacity
SOH
State of health
The
Power Cabinet N
data in the system running is the same as the
Battery Info
data in the power unit
running.
Table 4-11
Total runtime
Item
Description
Bypass runtime (h)
Time for which the UPS runs in bypass mode.
Inv. runtime (h)
Time for which the UPS runs in inverter mode.
The value must be an integer. For example:
If the value is less than 1, the value takes 0.
If the value is greater than or equal to 1 and less than 2, the value takes 1.