UPS5000-S-1600 kVA
User Manual
4 User Interface
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
131
USB Operations
Figure 4-33
USB operations
Starting or Shutting Down the Inverter
Item
Description
Inv. ON
The
Inv. ON
screen allows you to start the inverter
manually.
Inv. OFF
The
Inv. OFF
screen allows you to shut down the
inverter manually.
Battery Maintenance
Perform battery maintenance when no alarm is active on the UPS. Otherwise, the UPS
may supply no power.
A proportion of battery capacity will discharge during battery maintenance. This reduces
the discharge time before the next charge.
Do not perform battery maintenance when a D.G. is connected.
Perform battery maintenance periodically to increase the battery lifespan and improve the
UPS reliability. Battery maintenance includes
Forced Equalized Charging
,
Shallow Dis.
Test
, and
Capacity Test
. The next maintenance time displayed on the screen indicates the
upcoming time in which to check batteries.