UPS5000-S-1600 kVA
User Manual
4 User Interface
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
136
Step 3
Enter
https://UPS IP address
in the address box of the browser, select a language, set
User
name
and
Password
, and click
Login
.
The preset UPS IP address is 192.168.0.10. You can set the UPS Ethernet IP address on the LCD or
WebUI. The value range is 1.0.0.0–223.255.255.255.
Table 4-20
User description
Default User
Preset
Password
User Rights
admin (system
administrator)
Changeme
Performs all operations on the LCD and WebUI,
including system running information browsing,
system information exporting, parameter setting,
system control, system configuration, and system
maintenance.
operator
(common user)
Changeme
Only browses the system running information, exports
system information, starts/shuts down the inverter,
rectifies faults, and controls the buzzer. Other control
and maintenance functions that may affect system
operation are invisible and parameters cannot be set.
browser
(browsing user)
-
Only browses the system running information.
If an incorrect password is entered five consecutive times, the account will be logged out for 5
minutes.
After a user logs in to the WebUI, if another user logs in with the same user name, the current
account will be logged out.
It is advised to change the password after the first login using
User Mgmt.
on the
Config.
page to
prevent unauthorized access.
----End