UPS5000-S-1600 kVA
User Manual
4 User Interface
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
139
Item
Description
Default Value Value Range
Bus Capa. life
If this parameter is set to
Enable
,
the UPS detects the bus capacitor
lifespan.
Disable
Disable, Enable
Pre-warn. time
for bus capa.
life (mon)
Indicates the time when a
warning about bus capa. life
needs to be raised in advance
before the bus capa. life ends.
12
1–24
Paral. sys.
hibernate
When customer loads are light,
enable parallel hibernation to
alternate modules in hibernation
mode, which can prolong their
service life and improve the
system efficiency.
Disable
Disable, Enable
Module cycle
hiber. period
(d)
Indicates the rotation interval of
modules in hibernation mode.
The default value is 30, which
means that the hibernating
module is rotated every 30 days.
30
1–100
D.G. ECO
bypass supply
Indicates whether ECO bypass is
allowed to supply power in D.G.
mode. When the D.G. is
connected to the dry contact
signal GEN:
If this parameter is set to
Enable
, the system can enter
ECO bypass mode when the
D.G. supplies power to the
bypass and the ECO function
is enabled.
If this parameter is set to
Disable
, the system is not
allowed to enter ECO mode
when the D.G. supplies power
to the bypass.
Enable
Disable, Enable
RAM
verification
Enable or disable the memory
check function. If this parameter
is set to
Enable
, the control chip
RAM working status is checked
regularly. If this parameter is set
to
Disable
, regular check is
disabled.
Disable
Disable, Enable
Record time
after fault
Indicates the time for storing
fault data after the UPS
experiences a fault. The default
value is 0 ms, which means that
the data during 20 ms before the
fault occurs is recorded. If the
value is set to 40 ms, it means
0 ms
0 ms, 20 ms, 40
ms, 60 ms, 80
ms