UPS5000-S-1600 kVA
User Manual
4 User Interface
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
140
Item
Description
Default Value Value Range
that the data during 20 ms before
the fault occurs and the data
during 40 ms after the fault
occurs are recorded, and the like.
Collect
real-time site
waveform
If this parameter is set to
Enable
,
one waveform can be stored
manually.
Disable
Disable, Enable
Fan life
Indicates the life detection for
fans in the power modules and
bypass module.
Enable
Disable, Enable
Pre-warn. time
for fan life
(mon)
Indicates the time when a
warning about fan life needs to
be raised in advance before the
fan life ends.
12
1–24
Input Settings
Item
Description
Default Value Value Range
Input
adaptability
The value of
Input adaptability
can be
Strong
or
Weak
. Strong
input adaptability applies to the
D.G. or input sources whose
input current has high frequency
oscillation. In this mode, the total
distortion of the input current
waveform (THDi) is poor, but
the system is stable. Weak input
adaptability is suitable for mains
and AC input sources.
Strong
Strong, Weak
Output Settings
Item
Description
Default Value Value Range
Zero display
with no load
output
If this parameter is set to
Enable
,
the output current and output
load ratio are displayed as
< 3%
in the case of no load. If this
parameter is set to
Disable
, the
output current and output load
ratio are not displayed as 0 in the
case of no load.
Enable
Disable, Enable
Output
interruption
transfer time
The interruption for the UPS to
transfer from inverter mode to
bypass mode is 0–2 ms, and from
0
0 ms, 40 ms, 60
ms, 80 ms, 100
ms, 120 ms