UPS5000-S-1600 kVA
User Manual
5 Operations
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
166
Set
Battery capacity
correctly after double check. Incorrect settings affect the charging
power. The battery capacity of each power unit is the capacity of battery strings connected
to the power unit. If you are not sure how to determine the battery capacity, contact
Huawei technical support.
High or low charging power tends to shorten the battery lifespan, or even damages
batteries.
Figure 5-1
Settings Wizard
Set the time and date correctly. Incorrect time and date will cause false fault analysis during
maintenance or repair.
After you set network parameters, connect the UPS to the network over a network cable, which
enables you to remotely manage the UPS. If you do not need remote management, retain the default
network parameter settings.
Step 2
(Optional) On the LCD of the system, choose
System Info
>
Settings
>
DST Settings
and set
the DST mode as required.
Step 3
After you set parameters on the
Settings Wizard
screen, the system displays the
Bypass
mode
and
No battery
alarms, which do not need to be handled. If there is any other alarm,
you need to rectify the fault.