UPS5000-S-1600 kVA
User Manual
5 Operations
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
174
Figure 5-11
Abnormal bypass
Step 2
After the inverter shuts down, turn off the downstream output switch.
Step 3
Turn off the battery string circuit breaker of each power unit. If there are multiple battery
strings, turn off the general circuit breaker between battery strings and the UPS and then turn
off the circuit breaker for each battery string.
Step 4
Turn off the UPS input circuit breaker Q1-1, Q1-2 and Q1-3 and output circuit breaker Q5-1,
Q5-2 and Q5-3.
Step 5
Turn off the upstream bypass and mains input switches for the UPS.
----End
5.3 Battery Cold Start
Procedure
Step 1
Ensure that batteries have been connected properly. Use a multimeter to check that the voltage
of a battery string is greater than a certain value (single battery voltage x number of batteries
in the battery string).
Step 2
Turn off input switches Q1-1, Q1-2 and Q1-3 and the upstream bypass input switch. Turn on
the battery circuit breaker. If there are multiple battery strings, turn on the circuit breaker for
each battery string and then the general circuit breaker between battery strings and the UPS.
Step 3
Use a multimeter to check that the voltage of battery strings at the UPS end is greater than a
certain value (single battery voltage x number of batteries in the battery string), which
indicates that the batteries are connected properly.
Step 4
Press and hold down the
BATT START
button on the bypass module for at least 2 seconds.
The system automatically enters the battery cold start status. The LCD displays the Huawei
logo and an initialization progress bar.
Step 5
After LCD initialization, start the inverter.
----End