47
Specifications
Dimensions (H x W x D): 175 mm x 264 mm x 40 mm
2.4 Typical configurations
Table 2-18
Typical UPS configurations
Configuration
Application Scenario
Single UPS
Supplies power to common loads.
Dual-bus system
The dual-bus system is suitable for scenarios where high availability
requirements are posed for power supply. The dual-bus system
supplies power to important loads in large- and medium-sized
equipment rooms and data centers.
In addition to common parallel system advantages, the dual-bus
system also provides outstanding availability and eliminates
bottleneck failures. However, configuration of the dual-bus system is
complex.
2.4.1 Single UPS
This series uses a modular design in which multiple power modules are connected in parallel
to deliver a high loading capacity. If a single power module is faulty, the other power modules
continue working. When the load power is small, even a single UPS can provide redundant
capacity, which ensures high reliability.
2.4.2 Single UPS Dual-Bus System
The dual-bus system consists of two independent UPS systems. One of the two UPS systems
is a master system, and the other is a slave system. This design makes the dual-bus system
highly reliable and suitable for loads with multiple input terminals. An optional static transfer
switch (STS) can be installed to start the bus synchronization controller (BSC). The UPS
systems work in normal mode or bypass mode. The conceptual diagram uses a dual-bus
system with a single UPS as an example.