UPS5000-S-1600 kVA
User Manual
3 Installation
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
77
If the power units do not share battery strings, you need to install battery grounding
failure detectors in both power units.
Procedure
Step 1
Remove the top cover from the power unit, and remove the bracket of the battery grounding
failure detector.
Figure 3-41
Removing the cover and bracket
Step 2
Mount the battery grounding failure detector onto the bracket and reinstall the bracket in the
cabinet.
Figure 3-42
Installing a battery grounding failure detector
Step 3
Remove the front panel from the SPD in the bypass unit.
Step 4
Connect cables.
1.
Connect the power cables of the battery grounding failure detector to copper bars U and
N on the top of each power unit cabinet.