UPS5000-S-1600 kVA
User Manual
3 Installation
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
92
Table 3-10
DIP switch address mapping 2 (battery temperature sensor)
Toggle
Switch
23
24
25
26
27
28
29
30
1
1
0
1
0
1
0
1
0
2
1
0
0
1
1
0
0
1
3
1
0
0
0
0
1
1
1
4
0
1
1
1
1
1
1
1
5
1
1
1
1
1
1
1
1
6
0
0
0
0
0
0
0
0
3.4 Remote EPO
Huawei does not provide the EPO switch or cable. If the cable is required, the
recommended cable is 22 AWG.
Equip the EPO switch with a protective cover to prevent misoperations, and cover the
cable with protective tubing.
Triggering EPO will shut down the rectifier, inverter, charger, and static bypass, but does
not disconnect the UPS mains input. To power off the UPS completely, open the front-end
input switch when triggering EPO.
Connect the requisite EPO switch to the bypass unit dry contacts
Figure 3-68
Cable connection for an NC EPO switch