UPS5000-S-1600 kVA
User Manual
3 Installation
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
93
Figure 3-69
Cable connection for an NO EPO switch
When the EPO switch is in the NC state, remove the jumper between EPO_NC and EPO_12V
before connection. When the EPO switch is turned off, EPO is triggered.
When the EPO switch is in the NO state, ensure that the jumper is connected between EPO_NC and
EPO_12V. When the EPO switch is turned on, EPO is triggered.
3.5 Parallel System Installation
3.5.1 Connecting Power Cables
Procedure
Step 1
Ground each UPS in a parallel system separately, and connect power cables and battery
cables.
Step 2
Connect cables to the parallel system.