UPS5000-S-1600 kVA
User Manual
3 Installation
Issue 04 (2020-03-03)
Copyright © Huawei Technologies Co., Ltd.
95
Figures show only the CM, which stands for the UPS.
Figure 3-71
Connecting signal cables in a single UPS dual-bus system
(1) Control module 1 of the bypass unit in
UPS 1
(2) Control module 1 of the bypass unit in
UPS 2
Connecting Other Signal Cables
Connect signal cables for each UPS.
3.6 Installation Verification
Table 3-11 lists check items.
If the check results of listed items 8 and 9 in Table 3-11 do not meet the acceptance criteria,
the UPS may be damaged.
Table 3-11
Installation checklist
No.
Item
Acceptance Criteria
01
UPS installation
The UPS is securely installed and does not tilt due to
vibration.
02
Neat arrangement
The UPS and its adjacent cabinets are neatly arranged
and secured with connecting plates.
03
Layout of the busway
and cables
The busway and cables are routed properly as required
by the customer.
04
Labels on the busway
Both ends of a busway and cable are labeled. Labels are