2.3.5.3 Dry Contact Extended Card
Appearance
Figure 2-24
Dry contact extended card
Functions
The dry contact extended card provides five relay dry contact outputs and five signal input
ports. It implements abundant alarm and control functions to meet customer requirements.
For dry contact outputs, the rated DC voltage and current are 24 V DC and 0.6 A and the
maximum values are 30 V DC and 1.0 A. The rated AC voltage and current are 24 V AC and
0.6 A and the maximum values are 30 V AC and 1.0 A. During cable connection, ensure that
the voltage and current do not exceed these maximum values.
DO_1–DO_5 can indicate critical alarms, minor alarms, bypass mode, battery mode, low
battery voltage, D.G. control, and other status. DO_1 indicates low battery voltage by
default and others are reserved.
DI_1 and DI_2 allow you to monitor door alarms and water alarms.
All DIs are reserved. Users can flexibly set DOs based on actual requirements.
DI ports detect input dry contact signals which are passive signals.
DOs transmit passive dry contact output signals. Users need to connect external power supply to
DOs.
Table 2-14
Dry contact description
Dry Contact
Silk
Screen
Description
Output
DO_1
NO
Indicates relay output signals. The dry contact is
normally open by default. When the preset status
occurs, the relay is closed. Users can set the dry
contacts to normally open or closed based on
actual requirements.
COM
DO_2
NO
Indicates relay output signals. The dry contact is
normally open by default. When the preset status
occurs, the relay is closed. Users can set the dry
COM