UPS5000-S-300 kVA User Manual
(3P3W, 200 V)
4 User Interface
Issue 01 (2020-03-06)
Copyright © Huawei Technologies Co., Ltd.
93
Output Settings
Figure 4-21
Output settings
Item
Description
Default Value Value Range
Output voltage
level (V)
Specifies the system output
voltage level. This parameter is
configurable only after the
inverter shuts down. After you
change the voltage level, the
upper limit of the bypass voltage
restores to the default value.
200
200
Output volt.
adjustment (V)
The output voltage can be
slightly adjusted based on the
onsite power distribution
condition to ensure a minimum
difference between the output
voltage and the bypass voltage
and facilitate uninterruptible
power supply when the UPS
transfers from normal mode to
bypass mode.
200.0
190–210
Output
frequency (Hz)
Specifies the system output
frequency level.
50 Hz
50 Hz, 60 Hz
Output freq.
track rate
(Hz/s)
This parameter can be adjusted
based on site requirements. If
Output freq. track rate (Hz/s)
is slow, the inverter frequency is
different from the bypass
frequency when the bypass
frequency changes. If output is
overloaded or the inverter is
faulty, an interruption (less than
20 ms) occurs when the UPS
transfers from normal mode to
bypass mode. If
Output freq.
track rate (Hz/s)
is fast, the
0.6 Hz/s
0.1 Hz/s to 2.0
Hz/s