UPS5000-S-300 kVA User Manual
(3P3W, 200 V)
4 User Interface
Issue 01 (2020-03-06)
Copyright © Huawei Technologies Co., Ltd.
97
Monitoring interface card (MUS05A): provides four routes of configurable output dry
contact signals.
Dry contact extended card (MUE07A): provides five routes of input signals and five
routes of output signals.
Item
Description
MUE05A connection
Specifies the MUE05A connection status. Independent
input signals can be enabled only when this parameter
is set to
Enable
.
Batter ground fault [BTG]
Enable or disable battery grounding fault detection.
D.G. connection [GEN]
Enable or disable D.G. connection detection.
BCB connection [OL]
Enable or disable BCB connection detection.
Battery breaker [STA]
Enable or disable battery circuit breaker status
detection.
PDC output breaker [OUT]
Enable or disable PDC output circuit breaker status
detection.
PDC maintenance breaker [MT]
Enable or disable PDC maintenance circuit breaker
status detection.
BP/SYSMT Switch
If the BP/SYSMT switch is set to
Enable
, the port has
dry contact signal access. Using the port depends on
the status of the BP/SYSMT switch.
BP/SYSMT switch function
If the BP/SYSMT switch is set to
Enable
, this
parameter is displayed on the screen. Set this
parameter to determine whether the port is used to
detect the status of the PDU bypass input switch, or
system maintenance switch.
SPD/SYSOUT Switch
If the SPD/SYSOUT switch is set to
Enable
, the port
has dry contact signal access. How a user uses the port
depends on the status of the SPD/SYSOUT switch.
SPD/SYSOUT switch function
If the SPD/SYSOUT switch is set to
Enable
, this
parameter is displayed on the screen. Set this
parameter to determine whether the port is used to
detect the status of the PDU input surge protector, or
system output switch.
MUE06A connection
Specifies the MUE06A connection status. If this
parameter is set to
Enable
, the mains and bypass
backfeed protection is enabled.
MUS05A DO_1 Action,
MUS05A DO_2 Action,
MUS05A DO_3 Action,
MUS05A DO_4 Action
Controls the status of DO ports on the MUS05A dry
contact card.
MUE07A DO_1 Action,
MUE07A DO_2 Action,
MUE07A DO_3 Action,
MUE07A DO_4 Action,
Controls the status of DO ports on the MUE07A
extended dry contact card.