UPS5000-S-300 kVA User Manual
(3P3W, 200 V)
4 User Interface
Issue 01 (2020-03-06)
Copyright © Huawei Technologies Co., Ltd.
101
Item
Description
Shallow Dis. Test
Partially discharge batteries. A shallow discharge test can
be conducted to test the battery loop reliability and
short-time discharge capacity when the batteries have not
discharged for a long time.
Capacity Test
Fully discharge batteries. A deep discharge test is
conducted to obtain the battery discharge performance
data.
USB Operations
You can export
Fault Data
, and perform
Upgrade Software
,
BSP Upgrade
,
Export Config.
,
and
Import Config.
with USB.