UPS5000-S-300 kVA User Manual
(3P3W, 200 V)
5 Operations
Issue 01 (2020-03-06)
Copyright © Huawei Technologies Co., Ltd.
132
After you set parameters on the
Settings Wizard
screen, choose
System Info
>
Settings
>
System
Setting
. Check that
System Capacity
,
Power module capacity
,
Requisite modules
, and
Redundant modules
match the actual values.
If dry contact signals are connected to the system, choose
System Info
>
Settings
>
Dry contacts
Set
and check that the connected dry contacts have been enabled and that the disconnected dry
contacts have been disabled.
If the system has connected to the remote EPO switch, you need to choose
Monitoring
>
Param.
Settings
>
System Settings
on the WebUI and check that
EPO detection
is set to
Enable
.
Step 4
View the system running diagram on the MDU to check that the UPS is working in bypass
mode.
----End
5.1.3 Starting the Inverter
Starting the UPS on the LCD
Step 1
Choose
Common Functions
>
Inv. ON
.
You can also start the inverter by choosing
System Info
>
Maintenance
>
Inv. ON
.
Step 2
In the displayed login screen, select a user name and enter the password.
Step 3
In the displayed dialog box, tap
Yes
to start the inverter.
----End
Starting the UPS on the WebUI
Step 1
Open a browser (Internet Explorer 11 for example) and choose
Tools
>
Internet Options
.
Step 2
Click the
Advanced
tab, check that
Use TLS 1.0
and
Use TLS 1.1
are selected, and then
click
OK
.