UPS5000-S-300 kVA User Manual
(3P3W, 200 V)
A Alarm List
Issue 01 (2020-03-06)
Copyright © Huawei Technologies Co., Ltd.
154
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
are incorrect.
0006-1
Mains undervoltage
Minor
The mains is not
normal.
The power
module sampling
circuit is not
normal.
Check whether the input voltage
(Vi) ranges from 138 V
(excluding 138 V) to 240 V in the
200 V AC voltage system. If not,
the mains monitoring circuit of
the power module may be faulty.
Replace the faulty module.
0010-1
Abnormal bypass
voltage
Minor
The bypass
voltage range is
not correctly set.
The bypass input
voltage is not
normal.
1.
Check the bypass input voltage
or cable connections with a
multimeter.
2.
Check the voltage system and
bypass voltage thresholds
configured on the LCD.
0010-2
The bypass
frequency range
is not correctly
set.
The bypass input
frequency is not
normal.
1.
Check the bypass input voltage
or cable connections with a
multimeter.
2.
Check the bypass input
frequency. Check the rated
frequency and frequency range
configured on the LCD.
0011-1
Bypass phase
reversed
Minor
The phase sequence
of the three-phase
bypass input is
reversed.
Check whether the cable phase
sequence is correct using a
multimeter. If no multimeter is
available, exchange the positions
of any two cables.
0020-1
Battery connected
reversely
Critical
Batteries are not
properly installed.
1.
Check whether battery
polarities are correctly
installed by using a
multimeter. If no, correct the
installation.
2.
Check whether the battery
input voltage of the UPS is
normal. If yes, the battery
sampling circuit of the power
module is faulty. Replace the
power module.
0021-1
Battery EOD
Critical
The battery voltage
reaches the EOD
voltage threshold
due to continuous
discharge.
If the BCB box is configured,
check whether the BCB box trips.
If it trips, close the BCB box
switch.
0022-1
No battery
Minor
There is no
battery string.
1.
Check that battery cables are
correctly connected.
2.
Check that the battery terminal