UPS5000-S-300 kVA User Manual
(3P3W, 200 V)
4 User Interface
Issue 01 (2020-03-06)
Copyright © Huawei Technologies Co., Ltd.
86
Item
Description
Default Value Value Range
configurable.
NAT mapping
NAT means network address
translation. If it is set to Disable,
Internet cannot access IP
addresses in the local area
network (LAN).
Disable
Disable, Enable
Figure 4-12
RS485 settings
Item
Description
Default Value Value Range
Address
This serial port address is
allocated by the user.
1
1–254
Baud rate
Select a baud rate to match the
user's network management
conditions onsite.
9600
9600, 19200,
115200
Parity mode
Verify the validity of RS485
communication characters. When
a device node adopts RS485
communication, ensure that the
parity modes for the device nodes
are set to the same mode.
None
None, Odd,
Even
Stop bit
Stop bit in the Modbus
communication frame format.
When the UPS is connected over
the serial port Modbus, set this
parameter based on the frame
format that the upstream device
Modbus supports.
1
1–2