UPS5000-S-300 kVA User Manual
(3P3W, 200 V)
3 Installation
Issue 01 (2020-03-06)
Copyright © Huawei Technologies Co., Ltd.
51
Step 4
Secure the cabinet to the expansion bolt holes on the ground using M12x60 expansion bolts.
Figure 3-7
Tightening expansion bolts
(1) Mounting holes on the floor
(2) Mounting holes on the channel steel
Step 5
Install the front, rear, left, and right anchor baffle plates.
Figure 3-8
Installing the front, rear, left, and right anchor baffle plates
----End
3.2.1.2 Installing the UPS on Channel Steel
Context