UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
4 User Interface
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
123
Item
Description
Default
Value
Value
Range
BCB
connection
[OL]
Enable or disable BCB connection detection.
Disable
Disable,
Enable
Batter
breaker [STA]
Enable or disable battery circuit breaker
monitoring.
Disable
Disable,
Enable
PDC output
breaker
[OUT]
Enable or disable PDC output circuit breaker
monitoring.
Disable
Disable,
Enable
PDC
maintenance
breaker [MT]
Enable or disable PDC maintenance circuit
breaker monitoring.
Disable
Disable,
Enable
BP/SYSMT
Switch
If the BP/SYSMT switch is set to
Enable
, the
port has dry contact signal access. Using the
port depends on the status of the BP/SYSMT
switch.
Disable
Disable,
Enable
SPD/SYSOUT
Switch
If the SPD/SYSOUT switch is set to
Enable
,
the port has dry contact signal access. How a
user uses the port depends on the status of the
SPD/SYSOUT switch.
Disable
Disable,
Enable
Figure 4-48
Dry Contact Set 3