UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
4 User Interface
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
126
Item
Description
Default
Value
Value Range
MUE07A
DO_5
Corresponds to signal of the output dry
contact DO_5 on the MUE07A.
None
h, Backup time < 2
h, Backup time <
2.5 h, Backup time
< 3 h,
MUE07A
DI_1 to
DI_5
Corresponds to signal of the input dry
contact DI on the MUE07A.
None
None, Door alarm,
Water alarm
User Settings
Set the date and time correctly. Incorrect time display in running and alarm information would
lead to analysis errors during maintenance or repair.
Figure 4-53
User Settings 1