UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
8 Technical Specifications
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
191
Table 8-5
Bypass input electrical specifications
Item
Specifications
Input system
Three-phase, three-wire, and PE; does not support Δ-type
transformer input; supports only Y-type transformer input
Rated input voltage
380 V AC/400 V AC/415 V AC/420 V AC/480 V AC (line
voltage)
Rated frequency
50 Hz or 60 Hz
Input frequency
±6 Hz (0.5–6 Hz, ±2 Hz by default)
Input system
The mains input and bypass input can share a power source or
use different power sources.
Table 8-6
Battery specifications
Item
Specifications
Battery voltage
360–600 V DC (30–50 batteries, 40 batteries by default). If
there are 36–39 batteries, the output power is derated to 90%. If
there are 30–35 batteries, the output power is derated to 80%.
Battery management
Intelligent battery management
Cold start
If a mains outage occurs, batteries can start the UPS to supply
power to loads.
Charger output power
Under rated conditions, the maximum charge power of a
module is 15 kW.
Battery string sharing
Battery string sharing is supported in a parallel system. No
battery string is shared by default.
Batteries with no neutral
wire
Supported
Charging voltage
Equalized charging voltage: 2.3–2.4 V/cell. The default
voltage is 2.35 V/cell.
Float charging voltage: 2.23–2.3 V/cell. The default voltage
is 2.25 V/cell.
End of discharge (EOD)
voltage
1.6–1.9 V/cell
Table 8-7
Output electrical specifications
Item
Specifications
Output system
Three-phase, three-wire, and PE
Voltage
380 V AC/400 V AC/415 V AC/420 V AC/480 V AC (line