UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
A Alarm List
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
195
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
normal.
configured on the LCD.
0010-2
The bypass
frequency range
is not correctly
set.
The bypass input
frequency is not
normal.
1.
Check the bypass input voltage
or cable connections with a
multimeter.
2.
Check the bypass input
frequency. Check the rated
frequency and frequency range
configured on the LCD.
0011-1
Bypass phase
reversed
Minor
The phase sequence
of the three-phase
bypass input is
reversed.
Check whether the cable phase
sequence is correct using a
multimeter. If no multimeter is
available, exchange the positions
of any two cables.
0020-1
Battery connected
reversely
Critical
Batteries are not
properly installed.
1.
Check whether battery
polarities are correctly
installed by using a
multimeter. If no, correct the
installation.
2.
Check whether the battery
input voltage of the UPS is
normal. If yes, the battery
sampling circuit of the power
module is faulty. Replace the
power module.
0021-1
Battery EOD
Critical
The battery voltage
reaches the EOD
voltage threshold
due to continuous
discharge.
If the BCB box is configured,
check whether the BCB box trips.
If it trips, close the BCB box
switch.
0022-1
No battery
Minor
There is no
battery string.
The battery
string is not
properly
installed.
The power
module battery
fuse is blown.
1.
Check that battery cables are
correctly connected.
2.
Check that the battery terminal
voltage is normal.
3.
Check that the battery fuse in
the power module is intact.
0025-1
Battery overvoltage
Minor
The configured
number of
batteries is less
than the actual
number.
The battery
neutral wire is
1.
Check whether battery
parameters are correctly set.
2.
If they are correctly set, certain
batteries may be faulty.
3.
Check whether the battery
neutral wire is correctly
connected.