UPS5000-S-880 kVA
User Manual (CMI)
B Alarm List
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
189
B
Alarm List
Alarm ID
(Alarm ID-
Alarm
Cause ID)
Alarm Name Severity
Cause
Solution
0001-1
Mains voltage
abnormal
Minor
Cable connections
are incorrect.
The mains is
abnormal.
The power module
is faulty.
The output or
battery is
incorrectly
grounded.
1.
Check whether cables to mains
are disconnected, loose, or
incorrectly connected.
2.
If cable connections are correct,
measure the mains voltage with a
multimeter. If the mains voltage
is greater than 280 V, the mains
input is abnormal; if the mains
voltage is less than 272 V, the
sampling circuit of the power
module is abnormal. Replace the
faulty module.
3.
Check whether the output or
battery is incorrectly grounded.
0001-2
Cable connections
are incorrect.
The mains is
abnormal.
The mains input
fuse for the power
module is blown.
1.
Check whether cables to mains
are disconnected, loose, or
incorrectly connected.
2.
If the cable connection is correct,
measure the mains voltage with
multimeter. If the mains voltage
is lower than 80 V, the mains
input is abnormal; if the mains
voltage is higher than 88 V, the
sampling circuit of the power
module or its fuse is abnormal.
Replace the module.
0001-3
The mains is
abnormal.
Check the mains.
0004-1
Mains ph.
Reversed
Minor
Cable connections are
incorrect.
Check cable connections.