UPS5000-S-880 kVA
User Manual (CMI)
B Alarm List
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
195
Alarm ID
(Alarm ID-
Alarm
Cause ID)
Alarm Name Severity
Cause
Solution
cable alarm
cable is faulty.
0584-4
The inter-rack
industrial-frequency
synchronization cable
is disconnected.
0085-1
EPO
Critical
The emergency power-
off (EPO) button is
pressed.
Restore the EPO button status. Start
the UPS after the alarm is cleared.
0086-1
Bypass
transfer times
limit
Minor
The system frequently
transfers to bypass
mode due to overload
timeout or load
impact.
Check the load.
0087-1
System
transfer-to-
bypass
Warning
The neighboring UPS
is abnormal and
transfers to bypass
mode.
Check the reason why the
neighboring UPS transfers to bypass
mode.
0088-1
Rack address
conflict
Critical
The configured rack
address conflicts with
another one.
Check the rack address setting.
0089-1
Rack output
overload
Minor
The load is
excessive.
The rack capacity
setting is not
appropriate.
Remove some loads or expand
the UPS power capacity if the
UPS is overloaded.
Check that the configured rack
capacity meets requirements.
0090-1
Dry contact
board fault
Critical
I2C communication of
the dry contact board
MUE05A fails.
Replace the dry contact board
MUE05A.
0090-2
I2C communication
with the dry contact
board MUE06A fails.
Replace the dry contact board
MUE06A.
0356
Battery mode
Minor
The UPS is working in
battery mode.
The running status is displayed. See
details about how to handle other
alarms.
0359
No power
supply
Warning
No power is supplied.
The running status is displayed. See
details about how to handle other
alarms.
0332
Output
disabled
Minor
The output is disabled.
The running status is displayed. See
details about how to handle other
alarms.
0337
PDF bypass
Critical
The bypass input
The running status is displayed.