Step 4 Remove the short-circuit terminals from the fan power port in the cable trough of
top air-flow cabinet 1 (with a fan transit unit and a power switch) based on the
number of top air-flow cabinets (1–4) that need to be connected to the UPS.
Figure 3-44 Removing a short-circuit terminal from the fan power port
Step 5 Connect fan power cables to each top air-flow cabinet.
NO TE
The 24-pin terminal cables can be connected to any 14-pin terminal in top air-flow cabinet
1.
UPS5000 Top Air-flow Cabinet
User Manual
3 Product Installation
Issue 02 (2022-01-19)