Figure A-42
Components of a cord end terminal and a power cable
A. Cord end terminal
B. Insulation layer of a power cable
C. Power cable conductor
Procedure
Step 1
Where the cross-section of cable conductor (C) is exposed, strip away a length L1 of
insulation layer (B), as shown in
. Recommended values of L1 are listed in
NOTICE
When stripping a power cable, be careful not to damage the cable conductor.
Figure A-43
Stripping a power cable (cord end terminal)
Table A-26
Mapping between the cross-sectional area of the conductor and the value of L1
Cross-
Sectional
Area of
Conductor
(mm
2
)
Value of L1 (mm)
Cross-Sectional
Area of Conductor
(mm
2
)
Value of L1 (mm)
1
8
10
15
1.5
10
16
15