Check Item
Specifications
Check Result
Floor drain
DN50 or larger, made of cast iron or
stainless steel
□ Passed □ Failed
Grounding
A general ground bar is configured in
the Converged Cabinet. The general
ground point in each cabinet connects
to the general ground bar in the
Converged Cabinet. The general ground
bar in the Converged Cabinet connects
to the floor ground bar or collective
ground bar.
□ Passed □ Failed
Water port
Condensate drain outlet: for draining
condensate from the smart cooling
product.
□ Passed □ Failed
Humidifier water pipe port: Connects to
external water pipes to supply water to
the humidifier.
□ Passed □ Failed
NO TE
If any of the requirements is not met, contact Huawei technical support.
NO TICE
The UPS can generate large leakage currents. A circuit breaker equipped with an
RCD is not recommended. If leakage protection is required, select a recommended
upstream circuit breaker for the smart module.
Table 4-4 Recommended circuit breaker (NetCol500)
Load
Recommende
d Cable and
Circuit
Breaker
Specification
s
One Cooling
Only Smart
Cooling
Product
Terminal
Specification
s
Earth
Leakage
Circuit
Breaker
≤ 8.5 kW
Circuit
breaker
specifications
MCB D63/3P
-
100 mA
Input power
cable
specifications
5 x 8 AWG
10 mm
2
cord
end terminal
-
FusionModule800 Smart Small Data Center
User Manual
4 Installation Guide
Issue 01 (2021-02-05)