NO TICE
● The weight of an ESM-48100B1 is about 44 kg. Check the load-bearing
capability of the rack tray before installation.
● The depth of an ESM-48100B1 is 396 mm. Check the rack depth before
installation.
● The ESM can be installed in a 19-inch rack with guide rails and a tray. Check
whether the load-bearing capability meets requirements.
● If multiple ESMs are installed, certain clearances should be reserved. The space
for each ESM should be at least 3 U. The ESMs cannot be directly stacked or
vertically placed.
● Install ESMs from bottom to top. It is advised to install ESMs on four layers.
Figure 4-79 Correct installation
----End
4.2.7.2 Installing a PDU2000
Context
The PDU2000 can be half-height, full-height, or horizontal. Select the PDU2000
model based on the project configuration.
FusionModule800 Smart Small Data Center
User Manual
4 Installation Guide
Issue 01 (2021-02-05)
Copyright © Huawei Technologies Co., Ltd.
158