Figure 4-106 T/H sensor configuration
●
If the total number of IT cabinets and network cabinets is greater than six,
four aisle T/H sensors are configured. Install two sensors on the front and rear
right posts of the Converged Cabinet, and the other two on the front and rear
right posts of the IT cabinet where the second or third NetCol is installed.
–
If the total number of IT cabinets and network cabinets is less than six,
the second NetCol is installed in the IT cabinet to the right of the
Converged Cabinet.
–
If more than six IT cabinets and network cabinets are configured, the
second or third NetCol is installed in the middle cabinet between the
Converged Cabinet and the farthest cabinet.
Figure 4-107 T/H sensor configuration (for an even number of cabinets)
Figure 4-108 T/H sensor configuration (for an odd number of cabinets)
–
Each IT cabinet or network cabinet is configured with two temperature
sensors.