4.2.9.9 Routing the Cable to a WLDS900 Water Sensor
If the water sensor is required, perform the following steps to install it.
Context
●
The water sensor is composed of the water detection cable (BOM number:
33010445), water detector (BOM number: 33010352), and conversion cable
(packed with the water detector).
●
The water detector is installed in the Converged Cabinet.
●
The water detection cable and water detector are interconnected using the
conversion cable.
●
A single water detection cable is 5 meters long. If a longer cable is required,
connect the male connector of a water detection cable to the female
connector of another. One water detector can be connected to a maximum of
nine water detection cables.
Figure 4-143 Detector positions
(1) Water detector
FusionModule800 Smart Small Data Center
User Manual
4 Installation Guide
Issue 01 (2021-02-05)
Copyright © Huawei Technologies Co., Ltd.
194