Figure 4-185 Direction for securing cable ties
4.3.2 Cable Routes
General Cable Route
NO TE
When routing cables, leave a distance of at least 100 mm between power cables and signal
cables.
The customer can purchase power cables as required. The recommended specifications of
mains input power cables are as follows:
● 7.5 kW and 8.5 kW loads (cable BOM code: 25030893): Electronic|Electric Cable,600V/
1000V,ZA-YJV,5x10mm
2
,Black(5Cores:Yellow,Green,Red,Blue,Black),80A,CE
FusionModule800 Smart Small Data Center
User Manual
4 Installation Guide
Issue 01 (2021-02-05)
Copyright © Huawei Technologies Co., Ltd.
219