Procedure
Step 1 Add a UPS2000G-L.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Add a UPS2000G-L.
Table 5-8 Adding a UPS2000G-L
Path
Parameter
Setting
Choose
System
Settings >
Device
Management
and click Add
Device. The
parameters
for adding
devices are
displayed.
Device
attribute
Select UPS from the drop-down list box.
Device Type
Select UPS2000G-L from the drop-down
list box.
Connect To
Select ECC800 from the drop-down list
box.
Communicati
ons Port
Select COM4 from the drop-down list box.
NOTE
The setting example indicates that the
UPS2000G is connected to the COM4 port on
the ECC800-Pro. If the UPS2000G is connected
to another port, enter the number of the
connected port.
Device
Address
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the UPS2000G-L based on the
actual situation.
3. Click Test Connect to check whether the UPS2000G-L connects to the
ECC800-Pro properly.
–
If the connection succeeds, click Confirm. The connected devices are
displayed in the Number of connected devices list.
–
If the connection fails, check whether the device is properly connected to
the ECC800-Pro, whether the device and ECC800-Pro are running
properly, and whether the parameter settings are consistent with the
device parameters.
----End
5.3.8 Commissioning Sensors
5.3.8.1 Commissioning the Smoke Detector (Connected to the AI/DI Port on
the ECC800)
If a smoke sensor is installed, perform the following steps to commission it.